2024-11-01Last updated
All JET or TPL door controllers that are either connected to the same RS-485 channel or
found on the same LAN must use different physical addresses.
What you should know
The physical address must be a value from 0 - 31, and is set using the DIP switches on
the DDS controller. The DIP switches are labeled differently, depending on the model of the controller:
- For TPL controllers, the physical address is set with the DS2/1 and JP4/1 - 5 DIP
switches.
Note: If you have a TCP/IP extension board attached to the TPL controller, you
must remove it to access the DIP switches.
- For JET controllers, the physical address is set with the DS1/1 - 5 DIP switches.
The reader communication protocol is set using the JP4/6 - 8 DIP switches on TPL
controllers and the DS1/6 - 8 DIP switches on JET controllers. For example, for Wiegand to
read up to 50 bits without parity check on a TPL controller, set JP4/7 to 1 or ON. For more information, see the documentation from DDS corresponding
to your specific device.
Procedure
-
For TPL controllers, set DS2/1 to 1 or ON.
-
Set the physical address on the JP4/1 - 5 or DS1/1 - 5 DIP switches, according to the
following tables:
Example
To set the physical address of a TPL controller to 15, set DS2/1 to ON and JP4/1 - 5 to
ON ON ON ON OFF, respectively.To set the physical address of a
JET controller to 16, set DS1/1 - 5 to OFF OFF OFF OFF ON,
respectively.